Before Running the Gas Setup Program

(1) The Baud Rate of the Gas Pump_____ and the Crinds______.

(2) The Blend Ratio that is setup in the pumps______.

This information should be retrieved from the customers pump supplier.

In the Gas Setup Program Setup the  “System Parameters” Section

In the Gas Setup Program Setup the  “System Parameters” Section

Set the Baud Rate for both the Gas and Crinds in this section.

If you are setting up more than one type of dispenser and only 1 gas type has card readers, then setup the gas type of the one with card readers to Gas 1.

When setting up Crinds, the COM port for the Crinds should come before the dispenser port. This means if the Crind Port is set to COM3 the Gas Port should be set to COM4.

Tolkheim Products should be setup as follows

Tolkheim Products should be setup as follows

The Dispenser Setup is shown below

The Dispenser Setup is shown below

For all Tokheim pumps

Tier: 2

Level : 1

If Smart Fuel Terminal (SMF) -

Set Alpha to Yes

Set Credit to SMF

The Misc Setup is the same for most Dispenser types. It is important to check the following

The Misc Setup is the same for most Dispenser types. It is important to check the following

The “Auth Limit” must have an amount in it or credit cards will not process at the pumps.

Additional Information

Additional Information