CST BrandsHelpdesk Fuel SetupSite Controller Setup for Gilbarco Pumps

Site Controller Setup for Gilbarco Pumps

Before Running the Gas Setup Program

Before running the gas setup program, find out the following

(1) The baud rate of the Gas Pump PAM_____ and the Crinds______.

(2) Make sure there is a PAM on site

(3) The Blend ratio that is setup in the pumps______.

This information should be retrieved from the customers pump supplier.

In the Gas Setup Program Setup the  “System Parameters” Section

In the Gas Setup Program Setup the  “System Parameters” Section

Set the Baud Rate for both the Gas and Crinds in this section.

For Gilbarco Current Loop, the Baud Rate should be set to 4800.

If you are setting up more than one type of dispenser and only 1 gas type has card readers, then setup the gas type of the one with card readers to Gas 1.

When setting up Crinds, the COM port for the Crinds should come before the dispenser port. This means if the Crind Port is set to COM3 the Gas Port should be set to COM4.

Gilbarco Products should be setup as follows

The Dispenser Setup is shown below

The Dispenser Setup is shown below

Gilbarco pumps are not always setup as 1,2,3,4, sometimes they vary as shown above.

For Gilbarco Highland Pumps

Tier: 1

Level: 1

For all other Gilbarco pumps

Tier: 2

Level : 1

If Smart Fuel Terminal (SMF) -

Set Alpha to Yes

Set Credit to SMF

The Misc Setup is the same for most Dispenser types. It is important to check the following

The Misc Setup is the same for most Dispenser types. It is important to check the following

The “Auth Limit” must have an amount in it or credit cards will not process at the pumps.

0 Comments

Add your comment

E-Mail me when someone replies to this comment