BRCM2.64
BRCM2.64 Universal
Fiscal Systems will use model: PA0435200032
- Loop current selection (JP1C). Fiscal requires 45mA current loop so fully remove the jumper.
- RS422-A and RS422-B. This will where the ribbon cable will attach and each group has 2 jumpers to select TWI or RS422. Fiscal requires RS422 so both jumpers in JP_POS_A and JP_POS_B will be set to “A” or RS422.
- Loop configuration selection. This is where you will select single or dual input (this is the old single input, dual board or dual input, dual board). Group A can hold up to 8 loops (16 fueling positions) and Group B can hold up to 8 loops (16 fueling positions) or you can merge both groups into 1; 16 loops (32 fueling positions). Both jumpers on “A” will give single input, all 16 loops on 1 channel. Jumpers on “B” will give dual input, 2 separate sets of 8 loops.
- Communication lights. D19 (Group A) and D21 (Group B) are the “old” CR39. A solid D19/21 means no communication from Fiscal SC and a blinking D19/21 means communication from Fiscal SC. Once communication is established, D19/20 (Group A) and D21/22 (Group B) will both flash repeatedly.
- These are the individual channel loop isolation jumpers and corresponding activity lights.
- These are the Group A (1-8) loop connections.
- These are the Group B (9-16) loop connections. Depending on the jumper settings in section 3, these will either be a separate set of loops or combined with Group A.