BRCM2.64

BRCM2.64 Universal

Fiscal Systems will use model: PA0435200032

  1. Loop current selection (JP1C). Fiscal requires 45mA current loop so fully remove the jumper.
  1. RS422-A and RS422-B. This will where the ribbon cable will attach and each group has 2 jumpers to select TWI or RS422. Fiscal requires RS422 so both jumpers in JP_POS_A and JP_POS_B will be set to “A” or RS422.
  1. Loop configuration selection. This is where you will select single or dual input (this is the old single input, dual board or dual input, dual board). Group A can hold up to 8 loops (16 fueling positions) and Group B can hold up to 8 loops (16 fueling positions) or you can merge both groups into 1; 16 loops (32 fueling positions). Both jumpers on “A” will give single input, all 16 loops on 1 channel. Jumpers on “B” will give dual input, 2 separate sets of 8 loops.
  1. Communication lights. D19 (Group A) and D21 (Group B) are the “old” CR39. A solid D19/21 means no communication from Fiscal SC and a blinking D19/21 means communication from Fiscal SC. Once communication is established, D19/20 (Group A) and D21/22 (Group B) will both flash repeatedly.
  1. These are the individual channel loop isolation jumpers and corresponding activity lights.
  2. These are the Group A (1-8) loop connections.
  3. These are the Group B (9-16) loop connections. Depending on the jumper settings in section 3, these will either be a separate set of loops or combined with Group A.